•
•
•
•
•
Menu 3-2 Defrost Timer
DEFR.TIMER POS: XXXXX Entry Default
Defrost Timer XXX Defrost initiation via Input D11/12 (EXT) or
internal (INT)
↑,↓,(EXT,INT)
INT
Safe Defr Time XXX m Safe defrost time, i.e. max. allowed duration of
defrosting (internal defrost only)
0..180
150 min
Manual Defrost XXX Status (ON/OFF) of auxiliary manual defrost *)
↑,↓,(ON/OFF)
OFF
Def.Tim.Z2→ Separate defrost timer for zone 2 Menu 3-2-a
Defr. 1 xxxxx hh:mm Defrost start time for internal defrost; weekday,
time of day;
shown only when paramter defrost timer = INT
↑,↓,
(Mo-Su) or
numbers
(hh:mm)
Mo-Su
03:00
...
Defr. 14 xxxxx hh:mm
Menu 3-2-a Def.Tim.Z2
DEFR.TIMER POS: XXXXX Entry Default
Defrost Timer XXX Setting for how temperature zone 2 should defrost:
MitZ1 Together with zone 1
INT Internally
EXTExternally–thedefrostofboth
temperature zones is started
simultaneously via the external signal
↑,↓,
(ViaZ1(ViaZ1,
EXT,
INT)
ViatZ1
Safe Defr Time XXX m Safe defrost time, i.e. max. allowed duration of
defrosting
(internal defrost only)
0..120 60 min
Manual Defrost XXX Status (ON/OFF) of auxiliary manual defrost *) ↑,↓,
(ON/OFF)
OFF
Defr. 1 xxxxx hh:mm Defrost start time for internal defrost; weekday, time
of day;
shown only when paramter defrost timer = INT
↑,↓,
(Mo-Su) or
numbers
(hh:mm)
Mo-Su
01:00
...
Defr. 14 xxxxx hh:mm
*) Parameter is automatically set to ON at first start for the duration of the safe defrost time.