Menu 6-3 Cooling
COOLING POS: XXXXX Entry Default
corr.off to XX K Correction offset for pressure loss in suction line
IMPORTANT: in stand alone operation must be set to
”--”!
--, 0..20 2 K
Cont Cool Mon. XX m Continuous run monitoring --, 0..15 0 min
HG operation XXX Discharge gas mode
↑,↓,
(ON/OFF)
OFF
RetAirSensor→ Operation with four return air sensors →or Menu 6-3-a
EnablingRel XXX Switchingto“EnableOperation“:
OFFOpeningdegreeistransmittedviathesolid
state relay (SSR)
ONThetwoSSRsarenolongerclocking,they
are switched on if the case controller requires
refrigeration, i.e. switched off again if no refrigeration
is required.
↑,↓,
(ON/OFF)
OFF
Menu 6-3-a return air sensor
RET AIR SENSOR POS: XXXXX
Entry Default
Temp. R4.3
R4.3 instead R5.1
↑,↓,
(ON/OFF)
OFF
Temp. R4.4
R4.4 instead R5.2
↑,↓,
(ON/OFF)
OFF
Weighting R4.3
Weighting between R4.1 and R4.3
0..100
0 %
Weighting R4.4
Weighting between R4.2 and R4.4
0..100
0 %
Menu 6-4 Language
Selection is made according to entry. Checkmark shows current setting.
LANGUAGE POS: XXXXX Entry Default
DeutschD√
English GB
Francais F
Espanyol ESP
Finnish FIN
Cesky CZ