Firmware V3.13
21.04.2021
303/466
ALARMPRIOS POS: XXXXX Entry Default
emerg.cut-out SH Superheat drop below minimum level for duration of
delay time
-, 0..99
OD manual Valve opening degree defined by manual entry. Priority
applies to alarms VO Manual Zone 1, VO Manual Zone
2
-, 0..99 0
config:M/S w HG Configuration error: Simultaneous setting of parameters
for master-slave mode and discharge gas defrosting
-, 0..99 2
Check OD Alarm due to implausible opening degree
(see chapter Implausible opening position alarm)
-, 0..99 0
Extern.Alarm Alarm for registering external alarms, default text is
“CO2-Alarm”
-, 0..99 0
Menu 6-6 Em.Powersupply (Emergency Power supply)
EM.POW.SUP POS: XXXXX Entry Default
Cool.funct.OFF xxx Functionality of the cooling switched off during
emergency power supply? (Y/N)
↑,↓,
(Y/N)
N
Defr.funct.OFF xxx Functionality of the defrosting switched off during
emergency power supply? (Y/N)
↑,↓,
(Y/N)
N
Fan funct. OFF xxx Functionality of the fan switched off during emergency
power supply? (Y/N)
↑,↓,
(Y/N)
N
Frame fct.OFF xxx Functionality of the frame heater off during emergency
power supply? (Y/N)
↑,↓,
(Y/N)
N
Light fct. OFF xxx Functionality of the light during emergency power
supply? (Y/N)
↑,↓,
(Y/N)
N