EasyManua.ls Logo

ECKELMANN Case Controller UA 4 E Series - Page 312

ECKELMANN Case Controller UA 4 E Series
466 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Firmware V3.13
21.04.2021
312/466
Menu 1-3 Defrost Zone 1
DEFROST 1 XXXXX
Defrost X Displays current OFF/ON status of defrosting
Temp. R1.1 XXX °C Displays current evaporator defrost termination temperature Input Z31/Z32
Temp. R1.2 XXX °C Displays current evaporator defrost termination temperature Input Z81/Z82; shown
only when single-zone operation is set (Menu 6-1)
Def. End. Tmp. XXX °C Displays defrost termination temperature setpoint for comparison
Wait Time XX m Displays waiting time setpoint
Drip Time XX m Displays drip time setpoint
Last Defrst XX hh:mm Displays time (day, time of day) of last defrost cycle started
M/S Nof. Sl. Number of parameterised and accessible MA slaves
M/S Lost Sl. CAN address of the first MA slave which was not accessible during the last defrost
M/S Defr.Sl. Number of slaves currently undergoing a defrost
M/S DSlMat List of MA slaves currently undergoing a defrost
(can be scrolled through using ENTER)
DSq Nof. Sl. Number of DS slaves (only in the case of DS master)
DSq Lost Sl. CAN address of the first FA slave which was not accessible during the last defrost
DSq Defr.Sl. Number of slaves currently undergoing defrost
DSq DSlMat List of FA slaves currently undergoing a defrost
(can be scrolled through using ENTER)
Menu 1-4 Fan Zone 1
FANS 1 XXXXX
Fans XXX Displays current fan status
Temp. R1.1 XXX °C Displays current evaporator defrost termination temperature Input Z31/Z32
Fan Delay XXX °C Displays fan start temperature setpoint

Table of Contents

Related product manuals