Menu 3-2-a Def.Tim.Z2
DEFR.TIMER POS: XXXXX Entry Default
Defrost Timer XXX Setting for how temperature zone 2 should defrost:
MitZ1 Together with zone 1
INT Internally
EXTExternally–thedefrostofboth
temperature zones is started
simultaneously via the external signal
↑,↓,
(ViaZ1(ViaZ1,
EXT,
INT)
ViatZ1
Safe Defr Time XXX m Safe defrost time, i.e. max. allowed duration of
defrosting
(internal defrost only)
0..120 60 min
Manual Defrost XXX Status (ON/OFF) of auxiliary manual defrost *) ↑,↓,
(ON/OFF)
OFF
Defr. 1 xxxxx hh:mm Defrost start time for internal defrost; weekday, time
of day;
shown only when paramter defrost timer = INT
↑,↓,
(Mo-Su) or
numbers
(hh:mm)
Mo-Su
01:00
...
Defr. 14 xxxxx hh:mm
Menu 3-3 Setpoint Toggle
TOGGLE POS: XXXXX Entry Default
Status XXX Setpoint toggle for alternative set of setpoints
(setpoint set
toggle)
Toggle Setp. XXX Setpoint toggle via:
EXT digital input D21/22
INT= internal timer
CAN= CAN bus
„—"=deactivated
↑,↓,
(EXT, INT, CAN, --)
EXT
Toggle interv. X m The interval for the cyclical toggling between
standard and alternative setpoint data records; only
appears when the internal setpoint toggling is
activated (menu 3-3).
--, 10..60 –min
Alt ON: xxxxx hh:mm Start time for toggle to alternative set of setpoints,
weekday from-to DD-DD, time hh:mm; shown only
when internal setpoint toggle is activated (Menu 3-3)
↑,↓,
(Mo-Su) or
numbers
(hh:mm)
Mo-Su
21:00
AltOFF: xxxxx hh:mm End time for toggle to alternative set of setpoints,
weekday from-to DD-DD, time hh:mm; shown only
when internal setpoint toggle is activated (Menu 3-3)
↑,↓,
(Mo-Su) or
numbers
(hh:mm)
Mo-Su
05:00
Alt ON: xxxxx hh:mm Start time for toggle to alternative set of setpoints,
weekday from-to DD-DD, time hh:mm; shown only
when internal setpoint toggle is activated (Menu 3-3)
↑,↓,
(Mo-Su) or
numbers
(hh:mm)
Su
05:00