• Menu 2-2-1 Zone 1
DEFROST 1 POS: XXXXX Entry Default
Counting Rate X Setpoint of time during which evaporator defrost
termination temperature may be within band around
0°C before defrost counter counts down
0..15 0
Defrost Counter X Setpoint of count for number of defrost cycles to be
skipped. By pressing the ¿ key the value can be set to
1 until it is automatically reset to the basic settings.
1
Def. End. Tmp. XX °C Defrost termination temperature setpoint --, 0..30 10 °C
Wait Time XX m Waiting time setpoint between cooling and defrost 0..15 3 min
Drip Time X m Waiting time (drip time) setpoint between defrost and
cooling
0..15 5 min
2.Defrst Level XXX °C 2nd defrost stage setpoint; shown only when single-
zone operation is set (Menu 6-1)
--, -20..30 --
M/S Degiv.Fct. XXX Configuration of the defrost via CAN bus function.
For details see chapter Master/slavemode–defrost
synchronisation via CAN bus.
OFF,
MASTR,
SLAVE
OFF
M/S CAN Adr. XXX Selection of the controller (1..99) participating in the
defrost via CAN bus which is the master.
“--“,ifthiscontrollerisitselfmaster
(Parameter M/S Degiv.Fct.. = MASTR)
---, 1..99 --
DS-Function XXX Configuration of the defrost sequenz function (DS).
FordetailsseechapterDefrost sequenz (DS) via CAN
bus.
OFF,
MASTR,
SLAVE
OFF
DS-Group XXX Selection of which group a defrost sequenz of this
controller (1..99) belongs to.
---, 1..99 --
DS-Master XXX Selection of which controller (1..99) participating in the
defrost sequenz is the master.
“--“,ifthiscontrollerisitselfthemaster
(Parameter DS-Function = MASTR)
---, 1..99 --
DS-Wait time XXXm Wait time for the defrost sequenz 0..127 1 min