Firmware V3.13
21.04.2021
363/466
Menu 2-4-1 Zone 1
ALARM 1 POS: XXXXX Entry Default
High Temp Setp XX °C High temperature setpoint at which High
Temperature alarm is generated
-35..50 -12 °C
Low Temp Setp. XX K Temperature setpoint (difference below
temperature control setpoint) at which Low
Temperature alarm is generated
--, 0..10 2 K
Menu 2-4-2 Zone 2
ALARM 2 POS: XXXXX Entry Default
High Temp Setp XX °C High temperature setpoint at which High
Temperature alarm is generated
-35..50 -12 °C
Low Temp Setp. XX K Sollwert Temperatur (Differenz unter dem Sollwert
der Temperaturregelung), bei dem der Alarm
Untertemperatur ausgelöst wird
--, 0..10 2 K
Menu 2-4-3 Zone 1T Toggle
ALARM 1A POS: XXXXX Entry Default
High Temp Setp XX °C High temperature setpoint at which High
Temperature alarm is generated
-35..50 -12 °C
Low Temp Setp. XX K Temperature setpoint (difference below
temperature control setpoint) at which Low
Temperature alarm is generated
--, 0..10 2 K
Menu 2-4-4 Zone 2T Toggle
ALARM 2A POS: XXXXX Entry Default
High Temp Setp XX °C High temperature setpoint at which High
Temperature alarm is generated
-35..50 -12 °C
Low Temp Setp. XX K Temperature setpoint (difference below
temperature control setpoint) at which Low
Temperature alarm is generated
--, 0..10 2 K
Menu 2-5 Frame Heater
FRAME HTR POS: XXXXX
1 Mode frm htr Move to menu 2-5-1
2 Setpoint frm htr Move to menu 2-5-2
3 Mode altern. Move to menu 2-5-3; not shown when setpoint toggle is deactivated (Menu 3-3)
4 Setpoint altern. Move to menu 2-5-4; not shown when setpoint toggle is deactivated (Menu 3-3)
Menu 2-5-1 Mode frm htr
Selection is made according to entry. Checkmark shows current setting.