EasyManua.ls Logo

ECKELMANN Case Controller UA 4 E Series - Page 365

ECKELMANN Case Controller UA 4 E Series
466 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Firmware V3.13
21.04.2021
365/466
Menu 2-5-2 Frame Setpoints
SETPOINTS POS: XXXXX Entry Default
Mod: xxxxxxxxxxxx Displays set pane mode (Menu 2-5-1) fixed run time
Run Time XXX % Fixed on time; shown only when mod is set to
Fixed OT (Menu 2-5-1)
--, 0..100 100 %
emerg.run time XXX % On time in loss of humidity or room air
temperature (via CAN bus); shown only when
mode set to Enthalpy Control (Menu 2-5-1)
--, 0..100 100 %
enthalp. offs. XXX % Offset for on time when enthalpy control is
activated (via CAN bus); shown only when mode
set to Enthalpy Control (Menu 2-5-1)
-50..50 0 %
Invert Output xxx Inversion of the function of the frame heater
output
(terminals 91/92)
↑,↓
(ON/OFF)
ON
Menu 2-5-3 Toggle Mode
Selection is made according to entry. Checkmark shows current setting.
MODE ALT. POS: XXXXX Entry Default
Fixed run time
Enthalpy-ctrl rtm
Menu 2-5-4 Setpoint Toggle
TOG. SETP. POS: XXXXX Entry Default
Mod: xxxxxxxxxxxx Displays set pane mode (Menu 2-5-3) fixed run time
Run Time XXX % Fixed on time; shown only when mod is set to
Fixed OT (Menu 2-5-3)
--, 0..100 100 %
emerg.run time XXX % On time in loss of humidity or room air
temperature (via CAN bus); shown only when
mode set to Enthalpy Control (Menu 2-5-3)
--, 0..100 100 %
enthalp. offs. XXX % Offset for on time when enthalpy control is
activated (via CAN bus); shown only when mode
set to Enthalpy Control (Menu 2-5-3)
-50..50 0 %

Table of Contents

Related product manuals