1.
2.
3.
4.
Menu 6-2-4 230V Inputs
230V INPUT POS: XXXXX Entry Default
Entry1: XXXXXXXXXX Function of digital input 1 D11/D12 1) DEFR.TIMER
Entry2: XXXXXXXXXX Function of digital input 2 D21/D22 2) TOGGLE SETP.
Entry3: XXXXXXXXXX Function of digital input 3 D31/D32 3) DOOR CONTACT
Entry4: XXXXXXXXXX Function of digital input 4 D41/D42 4) Extern.Alarm
XXXXXXXXXXXXXXXXXXX Freely configurable alarm text for digital input
4,
thedefaulttextis“CO2-Alarm”
Text CO2-ALARM
Inv. D1 XXX Inverting of digital input 1 ↑,↓,
(ON/OFF)
OFF
Inv. D2 XXX Inverting of digital input 2 OFF
Inv. D3 XXX Inverting of digital input 3 OFF
Inv. D4 XXX Inverting of digital input 4 OFF
Possible settings for the digital inputs:
DEFR.TIMER Defrost timer*
MANUAL OFF. Manual shutoff both zones
MANUAL OFF. Z1 Manual shutoff only Z1
MANUAL OFF. Z2 Manual shutoff only Z2
TOGGLE SETP. Toggle setpoint
TOGGLE SETP Toggle setpoint *
DOOR CONTACT Door contact
MANUAL OFF Manual shutoff both zones
MANUAL OFF. Z1 Manual shutoff only Z1
MANUAL OFF. Z2 Manual shutoff only Z2
DOOR CONTACT Door contact *
MANUAL OFF Manual shutoff both zones *
MANUAL OFF. Z1 Manual shutoff only Z1
MANUAL OFF. Z2 Manual shutoff only Z2
EXT ALARM External Alarm *
MANUAL OFF Manual shutoff both zones
MANUAL OFF. Z1 Manual shutoff only Z1
MANUAL OFF. Z2 Manual shutoff only Z2
TOGGLE SETP Toggle setpoint
* Factory setting
Menu 6-2-5 Sensor Type
Selection is made according to entry. Checkmark shows current setting.
ATTENTION
Damage to the system and stock loss!Onlytrainedpersonnelshouldbeallowedtochangedigital
inputs, as chenges can affect other functions.