EEV ZONE 1 POS: XXXXX Entry Default
inject.time XX.X m Injection time following the switching on of the
controller or following a defrost or in the event of
a blockade of the regulation.
The value entered must not be greater than the
current”setuptime”parameter,otherwisethe
largest valid value will be used.
Furtherdetailsabout“Fixedvalveopeningdegree
inpumpdown/feed-inphase”seechapterFixed
valve opening degree in pumpdown/feed-in
phase.
0..100.0 0.5 min
OD over CAN XXX Send opening degree via CAN bus
(is employed when a demand dependent setpoint
evaluation/toshiftviaconsumer”is
parameterised in the corresponding pack
controller)
↑,↓,
(ON/OFF)
ON
15s Archiv X A few statuses and values are additionally
archived at 15 second intervals in the system
centre / store computer when this parameter is
setto“J”.
WARNING: This setting increases the memory
requirement and should only be activated when
needed / for diagnostic purposes.
↑,↓,
(Y/N)
N
OD 3s interv XXX Select interval for output of opening degree.
OFF = 6s
ON = 3s
Control is suspended for 6 seconds when
toggling.
↑,↓,
(ON/OFF)
OFF
Reset I-Sum XXX Reset I-sum (to zero) if superheat drops below
setminimumforlongerthantimesetby”delay
minSH”parameter.
OFF = I-sum not reset to zero
ON = I-sum is reset to zero
↑,↓,
(ON/OFF)
ON
edit op.deg. XXX Manual entry of valve opening degree ↑,↓,
(ON/OFF)
OFF
op.deg. Z 1 XXX % Current valve opening degree Zone 1; can be
edited when manual entry is activated
0..100 Default by controller
Maximum OD xxx % Sets an upper limit to the opening degree output
by the case controller
20..100 100%
Lo Temp to xxK Monitoring of the t0 transmitted by the pack
controller for unsuitably low values
NOTE: Following commissioning this value can
besetto”-”.
10..60, -- 28K
to VS corr. XXX °C Displays current corrected suction pressure
temperature on pack controller (assigned by Pack
No.)