Menu 1-6 Not used with this controller type.
Menu 1-7 Cooling Zone 2
COOLING 2 XXXXX
Cooling XXX Displays current OFF/ON status of cooling
op.deg. Z 2 XX % Displays current valve opening degree Zone 2
OD med. 24h XX % Displays mean valve opening degree Zone 2 for past day
Temp. R4.2 XXX °C Displays current refrigerant temperature Input Z71/Z72
Setpoint R4.2 XXX °C Displays refrigerant temperature setpoint for comparison
Hystersis R4.2 XXX K Displays refrigerant temperature hysteresis setpoint; shown only when on-off
control is set (Menu 2-1-2)
SH Z 2 XXX °C Displays current superheat temperature Zone 2
sup air ctrl XXX Displays current OFF/ON status of supply or refrigerant control
MOP op. XXX Displays OFF/ON setpoint of MOP mode
Status hand XXX Status manual shutdown (ON/OFF)
Menu 1-8 Defrost Zone 2
DEFROST 2 XXXXX
Defrost XXX Displays current OFF/ON status of Defrost Relay 2
Temp. R1.2 XXX °C Displays current evaporator defrost termination temperature Input Z81/Z82
Def. End. Tmp. XXX °C Displays defrost termination temperature setpoint for comparison
Wait Time XX m Displays waiting time setpoint
Drip Time XX m Displays drip time setpoint
Last Defrst XX hh:mm Displays time (day, time of day) of last defrost cycle started