• Menu 6-2-3 Alarm Delay
ALARMDELAY POS: XXXXX Entry Default
Sensor Fault XX m Sensor break alarm delay 0..30 15 min
High/Low Temp. XX m High/low temperature alarm delay 0..150 90 min
No Defrost XX h No defrost alarm delay --, 2..168 --- h
Selfholding N Alarm latching with manual alarm cancelling (YES)
or automatic cancelling on send (NO)
↑,↓,
(Y/N)
N