Section 5847 User Instructions
Issue AL, July 24, 2006 Spec. Nos. 586505000 and 5865055000 (Model LMS1000)
Page 3-24 Chapter 3. Commands
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
ACK
Description: Tags a user to an alarm log entry that is not already acknowledged.
Command Level: 4
Syntax: ACK
Comments: The ACK command displays the same information that would be displayed
if you received a system alarm report. But it also tags your user ID number to those log
entries. Refer to the SET REPORT command for additional information concerning the
operation of the system alarm reporting function.
Notes: This command prevents a system alarm report from occurring (if that feature is
being used).
Related Commands: none
Example:
Command<4>: ACK
ACKNOWLEDGED ALARM LOG ENTRIES AS OF 11:24:27 ON 01/01/01.
Chan Description Class Occurred Ack Cleared
A0001.2H Analog Channel 1 MAJOR 01/01 11:24:04 8 01/01 11:24:23
R0001.Pg Relay Channel 1 MINOR 01/01 11:23:30 8 01/01 00:00:00
A0001.2H Analog Channel 1 MAJOR 01/01 11:22:54 8 01/01 11:22:59
B0001 Binary Channel 1 MINOR 01/01 11:22:46 8 01/01 00:00:00
A0001.2H Analog Channel 1 MAJOR 01/01 11:22:43 8 01/01 11:22:52