User Instructions Section 5847
Spec. Nos. 586505000 and 5865055000 (Model LMS1000) Issue AL, July 24, 2006
Chapter 3. Commands Page 3-25
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
ACO
Description: Displays active alarms that have their alarm indication canceled.
Command Level: 1
Syntax: ACO
AC
Comments: Only analog, binary, and function alarms can have their alarm indication
canceled. When it seems that a relay would be energized (because of its control
program) but is not, use this command to see if any alarms have been canceled. Then
compare this listing with the control programs to see if any of the canceled alarms may
have affected the output.
Notes: none
Related Commands: CLR ACO, SET ACO
Example:
Command<1>: ACO
The following alarms are cutoff:
Chan Description Value Units Alarm Limit and Class
A0001 Analog Channel 1 +20.4 Amps 20.0 H - Hi Limit 2 MAJOR
Chan Description Status Alarm Status / Class
B0001 Binary Channel 1 CO active MINOR