Section 5847 User Instructions
Issue AL, July 24, 2006 Spec. Nos. 586505000 and 5865055000 (Model LMS1000)
Page 3-62 Chapter 3. Commands
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Limit 3 Service Effect Code: NSA
Limit 3 Service Effect Code:
Limit 3 Alarm Class Number: 2
Condition Type: LOW
Condition Type:
Limit 3 Condition Description:
THIS VOLTAGE IS LOW
Condition Description:
THIS CURRENT IS LOW
Limit 4 Enabled: Yes
Limit 4 Enabled (Y or N):
Limit 4 Value: 50.0
Limit 4 Value: 100
Limit 4 Type: L
Limit 4 Type is High or Low (H or L):
Limit 4 Name: LVA2
Limit 4 Name: BELOW 100
Limit 4 Notification Code: MN
Limit 4 Notification Code:
Limit 4 Service Effect Code: NSA
Limit 4 Service Effect Code:
Limit 4 Alarm Class Number: 2
Condition Type: LOW
Condition Type:
Limit 4 Condition Description:
THIS VOLTAGE IS TOO LOW
Condition Description:
THIS CURRENT IS TOO LOW
Unit Text: VOLT
Unit Text: AMPS
Off Delay Time: 0s
Off Delay Time:
On Delay Time: 0s
On Delay Time: 15
Save changes (Y or N): Y
___________________________________________________________________________________
Command<6>: CONFIG F0001
FUNCTION CHANNEL CONFIGURATION AS OF 07:35:28 ON 02/09/96.
Chan Description Act Rpt Pol Unit Off-Dly-On
F0001 Function Channel 1 Y Y + Volt 0s 0s
Sub-access ID Montype Monfmt
FUNCTION1 DCVOLTS D
LIMITS CONFIGURATION
Limit / Name Class Condtype Ntfc Svef
70.00H HVA2 MAJOR TOOHIGH MJ SA
Condition Description
THIS VOLTAGE IS TOO HIGH
60.00H HVA1 MAJOR HIGH MJ SA
Condition Description
THIS VOLTAGE IS HIGH
50.00L LVA1 MINOR LOW MN NSA
Condition Description
THIS VOLTAGE IS LOW
40.00L LVA2 MINOR TOOLOW MN NSA
Condition Description
THIS VOLTAGE IS TOO LOW