Channel active (Y or N): Y
Name: Function Channel 1
Name:
Sub-access Identifier: FUNCTION1
Sub-access Identifier:
System Alarm Report mode: Y
System Alarm Report mode (Y or N):
Monitor type: DCVOLTS
Monitor type: DCAMPS
Monitor Value Format: Decimal
Set monitor value format to integer(I) or decimal(D): I
Limit 1 Enabled: Yes
Limit 1 Enabled (Y or N):
Limit 1 Value: 70.00
Limit 1 Value: 5000
Limit 1 Type: H
Limit 1 Type is High or Low (H or L):
Limit 1 Name: HVA2
Limit 1 Name: ABOVE 5000
Limit 1 Notification Code: MJ
Limit 1 Notification Code:
Limit 1 Service Effect Code: SA
Limit 1 Service Effect Code:
Limit 1 Alarm Class Number: 1
Condition Type: TOOHIGH
Condition Type:
Limit 1 Condition Description:
THIS VOLTAGE IS TOO HIGH
Condition Description:
THIS CURRENT IS TOO HIGH
Limit 2 Enabled: Yes
Limit 2 Enabled (Y or N):
Limit 2 Value: 60.00
Limit 2 Value: 4200
Limit 2 Type: H
Limit 2 Type is High or Low (H or L):
Limit 2 Name: HVA1
Limit 2 Name: ABOVE 4200
Limit 2 Notification Code: MJ
Limit 2 Notification Code:
Limit 2 Service Effect Code: SA
Limit 2 Service Effect Code:
Limit 2 Alarm Class Number: 1
Limit 3 Enabled: Yes
Limit 3 Enabled (Y or N):
Limit 3 Value: 50.00
Limit 3 Value: 500
Limit 3 Type: L
Limit 3 Type is High or Low (H or L):
Limit 3 Name: LVA1
Limit 3 Name: BELOW 500
Limit 3 Notification Code: MN
Limit 3 Notification Code:
Limit 3 Service Effect Code: NSA
Limit 3 Service Effect Code:
Limit 3 Alarm Class Number: 2
Condition Type: LOW