Section 5847 User Instructions
Issue AL, July 24, 2006 Spec. Nos. 586505000 and 5865055000 (Model LMS1000)
Page 3-66 Chapter 3. Commands
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Save changes (Y or N): Y
Enter Program Line:
L0001=B0001
___________________________________________________________________________________
Command<6>: CONFIG B0003
BINARY CHANNEL CONFIGURATION AS OF 07:35:53 ON 01/01/01.
Chan Description Act Rpt Cont Class Off-Dly-On
B0003 Binary Channel 3 Y Y CC 0s 0s
Sub-access ID Condtype Ntfc Svef
BINARY3 LOW CR SA
Condition Description
THIS IS RELAY CHANNEL B03'S CONDITION DESCRIPTION
Channel active (Y or N): Y
Name: Binary Channel 3
Name: FIRE ALARM!
Sub-access Identifier: BINARY3
Sub-access Identifier: RECT1
System Alarm Report mode: Y
System Alarm Report mode (Y or N):
Condition Type: LOW
Condition Type: FUSEOPERATE
Condition Description:
THIS IS RELAY CHANNEL B03'S CONDITION DESCRIPTION
Condition Description:
Notification Code: CR
Notification Code: MJ
Service Effect Code: SA
Service Effect Code: NSA
Alarm Condition: CC
Alarm Condition (CC or CO): CO
Alarm Class Number: 0 1
Off Delay Time: 0s
Off Delay Time: 20
On Delay Time: 0s
On Delay Time: 45
Save changes (Y or N): Y
___________________________________________________________________________________
Command<6>: CONFIG E0001
ENERGY MANAGEMENT CHANNEL CONFIGURATION AS OF 16:33:32 ON 01/01/01.
Chan Description Act Capacity Sht RFA TR Dsl
E0001 Energy Mngmt Rectifier 1 N 200.0 A33 B33 R33 N
Channel active (Y or N): Y
Name: Energy Mngmt Rectifier 1
Name:
Energy Mngmt Rectifier 1 Shunt = A0033
Energy Mngmt Rectifier 1 Shunt = A
Energy Mngmt Rectifier 1 Capacity: 200.0
Energy Mngmt Rectifier 1 Capacity:
Energy Mngmt Rectifier 1 RFA = B0033
Energy Mngmt Rectifier 1 RFA = B
Energy Mngmt Rectifier 1 TR lead = R0033
Energy Mngmt Rectifier 1 TR lead = R
Rectifier ON when Standby ON (Y or N):
Save changes (Y or N): Y
___________________________________________________________________________________

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson LMS1000 and is the answer not in the manual?

Emerson LMS1000 Specifications

General IconGeneral
BrandEmerson
ModelLMS1000
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals