User Instructions Section 5847
Spec. Nos. 586505000 and 5865055000 (Model LMS1000) Issue AL, July 24, 2006
Chapter 3. Commands Page 3-129
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
02-03 200A XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX 506401 34341122 2.0.2.0
02-04 --- open ---
02-05 --- open ---
02-06 --- open ---
02-07 --- open ---
02-08 --- open ---
02-09 --- open ---
02-10 --- open ---
CAN I/O Cards:
Pos. Description Spec. Number Ser. # FW Ver.
------------------------------------------------------------------------------
02-01 XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX RCB SPEC# 514348 67567872 2.0.4.0
02-02 XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX RCB SPEC# 514348 67633409 2.0.4.0
02-03 XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX RCB SPEC# 514348 67698946 2.0.4.0
02-04 --- open ---
02-05 --- open ---
02-06 --- open ---
02-07 --- open ---
MCA:
Description Spec. Number Ser. # FW Ver.
------------------------------------------------------------------------
this is the MCA 509478 2801621 1.0.0.14
System voltage is Averaged
Temperature sensor reporting
Temperature is measured in degrees : Celsius
System distribution loads A and B are activated
___________________________________________________________________________________
Command<6>: p lp s
LPS POWER SYSTEM SETTINGS AS OF 14:21:50 ON 12/10/03.
System Adjustment Setpoints
Description Value Units
Float Voltage 52.10 VDC
Test/Equalize Voltage 52.10 VDC
High Voltage Shutdown 57.60 VDC
Plant Current Limit 800 Amps
System Alarm Setpoints
Description Value Units
High Voltage #1 Alarm 55.60 VDC
High Voltage #2 Alarm 56.60 VDC
Battery on Discharge Alarm 51.10 VDC
Very Low Voltage Alarm 47.10 VDC
Total Load Overcurrent Alarm 5100 Amps
A Load Overcurrent Alarm 2600 Amps
B Load Overcurrent Alarm 2100 Amps
High Temperature #1 Alarm 99 DegC
High Temperature #2 Alarm 99 DegC
Low Temperature #1 Alarm -42 DegC
Low Temperature #2 Alarm -40 DegC