Section 5847 User Instructions
Issue AL, July 24, 2006 Spec. Nos. 586505000 and 5865055000 (Model LMS1000)
Page 3-130 Chapter 3. Commands
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
System Configuration Setpoints
Description Value Units
Audible Silent Time 10 Minutes
Manual Test/Equalize Time 2 Hours
Relay Test Time 20 Seconds
Auto Equalize Time Multiplier 1
Temperature Compensation Slope 0.090 VDC/DegC
Maximum Temp. Compensation Voltage 55.90 VDC
Minimum Temp. Compensation Voltage 50.05 VDC
___________________________________________________________________________________
Command<6>: p lp i
LPS interface is running
LPS EQUIPMENT INVENTORY AS OF 14:21:58 ON 12/10/03.
Bay 1 - LPS Bay #1
Spec. #: 1234567890123 S/N:-1294967295
Description Spec. Number Ser. # FW Ver.
------------------------------------------------------------------------
Bay Router 1-01:
This is the ROUTER on the MCA BD 509478 2801621 1.0.1.0
Dist. Panel 1-01:
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX 509525 50331648 2.0.3.0
Positions Element Type Load Description
01--02 Fuse B Fuse 01-01 Load
03--06 Fuse B Fuse 01-03 Load
07--12 Fuse B Fuse 01-07 Load
13--20 Fuse B Fuse 01-13 Load
21--24 Breaker B Breaker 01-21 Load
Dist. Panel 1-02:
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX 509525 50397185 2.0.3.0
Positions Element Type Load Description
25--26 Breaker B Breaker 01-25 Load
27--30 Breaker B Breaker 01-27 Load
31--36 Breaker B Breaker 01-31 Load
37--44 Breaker B Breaker 01-37 Load
45--48 --- open ---
PCU: -48 VDC Output
Pos. Cap. Description Spec. Number Ser. # FW
Ver.
---------------------------------------------------------------------------------
01-01 200A XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX 506401 33554432 2.0.2.0
01-02 --- open ---
01-03 --- open ---
01-04 --- open ---
01-05 --- open ---
01-06 --- open ---