Section 5847 User Instructions
Issue AL, July 24, 2006 Spec. Nos. 586505000 and 5865055000 (Model LMS1000)
Page 3-148 Chapter 3. Commands
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
[50% Battery On Discharge]
A9002 Vortex System Current +800 Amps [None/Overcurrent]
A9006 Vortex Shunt01 Current +200 Amps [None/Fail]
A9007 Vortex Shunt02 Current +200 Amps [None/Fail]
A9010 Vortex Shunt05 Current +200 Amps [None/Fail]
A9011 Vortex Shunt06 Current +200 Amps [None/Fail]
B9009 Vortex PCU Emergency Stop [None/Active]
B9024 Vortex PCU High AC Line [None/Active]
B9010 Vortex System Fuse [None/Active]
B9011 Vortex All AC Off [None/Active]
B9014 Vortex LVDs Inhibited [None/Active]
B9015 Vortex System Major [None/Active]
B9016 Vortex System Minor [None/Active]
VORTEX SUBSYSTEM STATUS AS OF xx:xx:xx ON xx/xx/xx.
Chan Description Value Units Alarm Status
A9003 Vortex Subsystem Voltage +50.9 VDC [None]
[High Voltage]
[Low Voltage]
A9004 Vortex Subsystem Current +400 Amps [None/Overcurrent]
A9008 Vortex Shunt03 +200 Amps [None/Fail]
A9009 Vortex Shunt04 +200 Amps [None/Fail]
B9021 Vortex Subsystem Fuse [None/Active]
B9022 Vortex Subsystem Major [None/Active]
B9023 Vortex Subsystem Minor [None/Active]
VORTEX PCU STATUS AS OF xx:xx:xx ON xx/xx/xx.
Chan Description Value Units Alarm Status
A9005 Total PCU Current +1200 Amps
A9026 PCU01 Current +100 Amps [None/Fail]
A9027 PCU02 Current +100 Amps [None/Fail]
A9030 PCU05 Current +100 Amps [None/Fail]
A9031 PCU06 Current +100 Amps [None/Fail]
A9043 PCU09 Current +100 Amps [None/Fail]
A9037 PCU12 Current +100 Amps [None/Fail]
A9045 PCU20 Current +100 Amps [None/Fail]
VORTEX MCA STATUS AS OF xx:xx:xx ON xx/xx/xx.
Description Alarm Status
Board Fail active
Shelf fuse active
A/D No System Voltage Input active
A/D No Sense Lead Voltage Input active
A/D No Subsystem Voltage Input active
Display Fail active
VORTEX LVD STATUS AS OF xx:xx:xx ON xx/xx/xx.
Description Alarm Status
LVD 1A [inhibited/failed/active/inactive]
LVD 1B [inhibited/failed/active/inactive]
LVD 2A [inhibited/failed/active/inactive]
LVD 2B [inhibited/failed/active/inactive]
LVD 3A [inhibited/failed/active/inactive]
LVD 3B [inhibited/failed/active/inactive]
The following is displayed only for active potentiometer controlled LVDs:
[LVD 3A] [active]
[LVD 3B] [active]
[LVD 4A] [active]