Command<1>: SCAN V SYSTEM
VORTEX SYSTEM STATUS AS OF xx:xx:xx ON xx/xx/xx.
Chan Description Value Units Alarm Status
A9001 Vortex System Voltage +50.3 VDC [None]
[High Voltage #1]
[High Voltage #2]
[Battery On Discharge]
[50% Battery On Discharge]
A9002 Vortex System Current +800 Amps [None/Overcurrent]
A9006 Vortex Shunt01 Current +200 Amps [None/Fail]
A9007 Vortex Shunt02 Current +200 Amps [None/Fail]
A9010 Vortex Shunt05 Current +200 Amps [None/Fail]
A9011 Vortex Shunt06 Current +200 Amps [None/Fail]
B9009 Vortex PCU Emergency Stop [None/Active]
B9024 Vortex PCU High AC Line [None/Active]
B9010 Vortex System Fuse [None/Active]
B9011 Vortex All AC Off [None/Active]
B9014 Vortex LVDs Inhibited [None/Active]
B9015 Vortex System Major [None/Active]
B9016 Vortex System Minor [None/Active]
___________________________________________________________________________________
Command<1>: SCAN V SUBSYSTEM
VORTEX SUBSYSTEM STATUS AS OF xx:xx:xx ON xx/xx/xx.
Chan Description Value Units Alarm Status
A9022 Vortex Subsystem Voltage +50.9 VDC [None]
[High Voltage]
[Low Voltage]
A9023 Vortex Subsystem Current +400 Amps [None/Overcurrent]
A9008 Vortex Shunt03 +200 Amps [None/Fail]
A9009 Vortex Shunt04 +200 Amps [None/Fail]
B9021 Vortex Subsystem Fuse [None/Active]
B9022 Vortex Subsystem Major [None/Active]
B9023 Vortex Subsystem Minor [None/Active]
___________________________________________________________________________________
Command<1>: SCAN V MCA
VORTEX MCA STATUS AS OF xx:xx:xx ON xx/xx/xx.
Description Alarm Status
Board Fail active
Shelf fuse active
A/D No System Voltage Input active
A/D No Sense Lead Voltage Input active
A/D No Subsystem Voltage Input active
Display Fail active
___________________________________________________________________________________
Command<1>: SCAN V LVD
VORTEX LVD STATUS AS OF xx:xx:xx ON xx/xx/xx.
Description Alarm Status
LVD 1A [inhibited/failed/active/inactive]
LVD 1B [inhibited/failed/active/inactive]
LVD 2A [inhibited/failed/active/inactive]
LVD 2B [inhibited/failed/active/inactive]