Section 5847 User Instructions
Issue AL, July 24, 2006 Spec. Nos. 586505000 and 5865055000 (Model LMS1000)
Page 3-244 Chapter 3. Commands
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SET VORTEX LVD RECONNECT
Description: Sets the low voltage disconnect "reconnect" value for all installed VPS low
voltage disconnect circuits.
Command Level: 6
Syntax: SET VORTEX LVD RECONNECT
SE V LVD REC
Comments: The current value is displayed, followed by a prompt to enter a new value.
Notes: The MCA does not allow an adjustment which could result in a service
interruption. Refer to the VPS instruction manual's low voltage disconnect "reconnect"
adjustment procedure for details.
The following message is displayed if the setting was not accepted by the MCA.
Power system did not accept the new value, setting remains
unchanged.
Related Commands: none
Example:
Command<6>: SET V LVD RECONNECT
LVD Reconnect Voltage: 49.00 VDC
LVD Reconnect Voltage: