User Instructions Section 5847
Spec. Nos. 586505000 and 5865055000 (Model LMS1000) Issue AL, July 24, 2006
Chapter 3. Commands Page 3-243
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SET VORTEX LVD DISCONNECT
Description: Sets the low voltage disconnect "disconnect" value for the selected VPS
low voltage disconnect circuit.
Command Level: 6
Syntax: SET VORTEX LVD[LVD_number][LVD_side] DISCONNECT
SE V LVD[LVD_number][LVD_side] DISC
Comments: The current value is displayed, followed by a prompt to enter a new value.
Notes: The MCA does not allow an adjustment which could result in a service
interruption. Refer to the VPS instruction manual's low voltage disconnect "disconnect"
adjustment procedure for details.
The following message is displayed if the setting was not accepted by the MCA.
Power system did not accept the new value, setting remains
unchanged.
Related Commands: none
Example:
Command<6>: SET V LVD1 DISCONNECT
Which LVD circuit(A or B)? A
LVD1A Disconnect voltage setting: 42.00 VDC
LVD1A Disconnect voltage setting:
___________________________________________________________________________________
Command<6>: SET V LVD2 DISCONNECT
Which LVD circuit(A or B)? B
LVD2B Disconnect voltage setting: 42.00 VDC
LVD2B Disconnect voltage setting:
___________________________________________________________________________________
Command<6>: SET V LVD3 DISCONNECT
Which LVD circuit(A or B)? B
LVD3B Disconnect voltage setting: 42.00 VDC
LVD3B Disconnect voltage setting:
___________________________________________________________________________________
Command<6>: SET V LVD2B DISCONNECT
No digitally controlled LVDs installed

Table of Contents