ERROR TYPE
(CHANNEL #)
DESCRIPTION/ACTION
Analog H/W
Configuration
Error
(B0095)
Description: Reported configuration of universal A/D point does not match configuration
stored in Network or Master Node I/O Subsystem.
Action: Determine the source channel via the ALARMS command. Enter the CONFIG
Axxxx command and verify the channel configuration is as desired. Be sure to save
changes even if none are made. Verify the error clears within 15 seconds.
Temperature
Probe Failure
(B0096)
Description: Temperature probe sensor has failed.
Action: Replace the temperature probe specified by the ALARMS command.