b) Identify the Discrete Output to be used for valve control.
c) Set Source to Batch Primary Valve.
d) Set Polarity to match the wiring.
The ON state of the Discrete Output must open the valve, and the OFF state must close the
valve.
e) Set Fault Action so that the valve will be closed if a fault occurs.
The appropriate setting is either Upscale or Downscale. The setting to use for your installation
depends on your valve type, your wiring, and your setting for Polarity.
4. Optional: For two-stage batching, assign one of the Discrete Outputs to the secondary valve.
You can also assign one of the Discrete Outputs to a pump when the batcher is configured for single
stage or two stage.
Configure a DO for valve control using the Field Communicator
Prerequisites
Channel B, Channel C, or Channel D must be available for valve control.
The selected channel must be wired to the valve.
The selected channel and the valve must be powered by a power supply, not by the transmitter.
Procedure
1. Verify the wiring between the selected channel and the valve.
2. Configure the selected channel to operate as a Discrete Output.
a) Choose Configure > Manual Setup > Inputs/Outputs.
b) Set Channel B, Channel C, or Channel D to operate as a Discrete Output.
c) Set Power Source to External.
3. Configure the selected channel for valve control.
a) Choose Configure > Manual Setup > Inputs/Outputs.
b) Select the channel to be used for valve control.
c) Select Discrete Output x.
d) Set Source to Primary Valve.
e) Set Polarity to match the wiring.
The ON state of the Discrete Output must open the valve, and the OFF state must close the
valve.
f) Set Fault Action so that the valve will be closed if a fault occurs.
The appropriate setting is either Upscale or Downscale. The setting to use for your installation
depends on your valve type, your wiring, and your setting for Polarity.
Configure process measurement applications Configuration and Use Manual
March 2019 MMI-20025166
100 Micro Motion Model 5700 Transmitters with Configurable Outputs

Table of Contents

Other manuals for Emerson Micro Motion 5700

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Micro Motion 5700 and is the answer not in the manual?

Emerson Micro Motion 5700 Specifications

General IconGeneral
Model5700
TypeTransmitter
Measurement PrincipleCoriolis
EnclosureAluminum or stainless steel
Output Signals4-20 mA
Communication ProtocolsHART
DisplayOptional LCD
Operating/Ambient Temperature Range-40 to 60 °C (-40 to 140 °F)
Materials of ConstructionStainless steel
Enclosure RatingIP67
Hazardous Area ApprovalsATEX, IECEx
DiagnosticsComprehensive diagnostics available