Cause
The connection to an external measurement device has failed. No external data is available.
Recommended actions
1. Verify that the external device is operating correctly.
2. Verify the wiring between the transmitter and the external device.
17.13.33 [116] Temperature Overrange (API referral)
Alert
Process Aberration
Cause
The line temperature is outside the range of the API table.
Recommended actions
1. Ensure that process temperature is within the range of the API table.
2. Verify the configuration of the API referral application and related parameters.
17.13.34 [117] Density Overrange (API referral)
Alert
Process Aberration
Cause
The line density is outside the range of the API table.
Recommended actions
1. Ensure that process density is within the range of the API table.
2. Verify the configuration of the API referral application and related parameters.
17.13.35 [118] Discrete Output 1 Fixed
Alert
Output Fixed
Cause
The output is configured to send a constant state. A loop test may be in progress.
Recommended actions
Check to see if a loop test is in process (the output is fixed).
Troubleshooting Configuration and Use Manual
March 2019 MMI-20025166
274 Micro Motion Model 5700 Transmitters with Configurable Outputs