5. Ensure that reference temperature and reference pressure, if applicable, are configured correctly.
6. Ensure that the selected API table is appropriate for the process fluid.
17.3 Batch problems
17.3.1 Batch will not start
Cause
Previous batch not ended
Valve is closed but the transmitter is detecting flow
No discrete output configured for batch control
For two-stage batching, primary and secondary valves are not configured
Recommended actions
1. End the batch.
2. Check for two-phase flow.
3. Verify the zero.
4. Verify the cutoffs.
5. Set up a channel to operate as a discrete output, and configure it for batch control.
6. For two-stage batching, configure the primary and secondary valves.
17.3.2 Valve operation is backwards
Cause
Discrete Output wiring is incorrect
Discrete Output polarity is reversed
Recommended actions
1. Verify the wiring between the Discrete Output and the valve. The ON signal must open the valve.
Perform a loop test.
2. Change the setting of Discrete Output Polarity.
17.3.3 Valve does not operate
Cause
Discrete Output wiring is incorrect
Discrete Output channel is set up for internal power
Recommended actions
1. Verify the wiring between the Discrete Output and the valve. The ON signal must open the valve.
Perform a loop test.
2. Ensure that the channel is wired and configured for external power.
Troubleshooting Configuration and Use Manual
March 2019 MMI-20025166
246 Micro Motion Model 5700 Transmitters with Configurable Outputs