Power supply problem
Wiring problem
Circuit failure
Channel not configured for desired output or input
Incorrect internal/external power configuration
Recommended actions
1. Check the power supply and power supply wiring.
2. Verify the output wiring.
3. Check the Fault Action settings.
4. Verify channel configuration for the affected mA output.
5. Contact customer service.
17.12.3 mAO below 4 mA
Cause
Incorrect internal/external power configuration
Output not powered
Open in wiring
Bad output circuit
Process condition below LRV
LRV and URV are not set correctly
Fault condition if Fault Action is set to Internal Zero or Downscale
Bad mA receiving device
Recommended actions
1. Check your process conditions against the values reported by the device.
2. Verify the receiving device, and the wiring between the transmitter and the receiving device.
3. Check the settings of Upper Range Value and Lower Range Value.
4. Check the Fault Action settings.
5. Verify channel configuration for the affected mA Output.
17.12.4 Constant mAO
Cause
Incorrect process variable assigned to the output
Fault condition exists
Non-zero HART address (mA Output 1)
A loop test is in progress