Emerson Micro Motion 5700 - Field Communicator Connection to Transmitter Terminals; Field Communicator Connection to Local HART Loop

Emerson Micro Motion 5700
356 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Figure C-1: Field Communicator connection to transmitter terminals
A. Field Communicator
B. 250–600 Ω resistance
C. External power supply, if required
D. Transmitter with end-cap removed
E. HART connection posts
2. To connect to a point in the local HART loop, attach the leads from the Field Communicator to any
point in the loop and add resistance as necessary.
The Field Communicator must be connected across a resistance of 250–600 Ω.
Figure C-2: Field Communicator connection to local HART loop
A. Field Communicator
B. 250–600 Ω resistance
C. External power supply, if required
D. Transmitter, with wiring compartment opened
E. HART connection posts
3. To connect to a point in the HART multidrop network, attach the leads from the Field Communicator to
any point on the network.
Configuration and Use Manual Using a Field Communicator with the transmitter
MMI-20025166 March 2019
Configuration and Use Manual 335