Options for Discrete Input Polarity
Polarity Discrete Input
power supply
Voltage Status of Discrete
Input at transmitter
Active High Internal Voltage across terminals is high ON
Voltage across terminals is 0 VDC OFF
External Voltage applied across terminals is
3–30 VDC
ON
Voltage applied across terminals is
<0.8 VDC
OFF
Active Low Internal Voltage across terminals is 0 VDC ON
Voltage across terminals is high OFF
External Voltage applied across terminals is
<0.8 VDC
ON
Voltage applied across terminals is
3–30 VDC
OFF
Integrate the meter with the control system Configuration and Use Manual
March 2019 MMI-20025166
164 Micro Motion Model 5700 Transmitters with Configurable Outputs