Issue/Rev. 0.2 (12/12) MN0M023 • Page 113
Device Functions Proline Promass 83 8 Block INPUTS
8.1.2 Function group OPERATION
INPUTS F
STATUS INPUT FAA
CONFIGURATION 500
OPERATION 504
Function description
INPUTS o STATUS INPUT o OPERATION
ACTUAL
STATUS INPUT
(5040)
Use this function to view the current level of the status input.
Display:
HIGH
LOW
SIMULATION STATUS
INPUT
(5041)
Use this function to simulate the status input, in other words to trigger the function
assigned to the status input (see the function ASSIGN STATUS INPUT (5000) on
page 112).
Options:
OFF
ON
Factory setting:
OFF
! Note!
• The “SIMULATION STATUS INPUT” message indicates that simulation is active.
• The measuring device continues to measure while simulation is in progress, i.e. the
current measured values are output correctly via the other outputs.
" Caution!
The setting is not saved if the power supply fails.
VALUE SIMULATION
STATUS INPUT
(5042)
! Note!
The function is not visible unless the function SIMULATION STATUS INPUT (5041) is
active (= ON).
Use this function to define the level to be assumed at the status output during the
simulation. This value is used to test downstream devices and the measuring device itself.
Options:
HIGH
LOW
Factory setting:
LOW
" Caution!
The setting is not saved if the power supply fails.