Issue/Rev. 0.2 (12/12) MN0M023 • Page 31
Device Functions Proline Promass 83 4 Block QUICK SETUP
4.3 Gas measurement Setup menu
A0002502-en
Settings for the Gas Measurement Setup menu:
Fct. code Function name Suggested settings Description
Call up through the function matrix:
B QUICK SETUP QUICK SETUP GAS MEASUR. see p. 25
1004 QUICK SETUP GAS MEASUR. YES see p. 25
Basic configuration:
6420 EMPTY PIPE DETECTION No entry possible, the selection changes
automatically to OFF.
see p. 125
6400 ASSIGN LOW FLOW CUT OFF For gas measurement we recommend
to switch off the low flow cut off.
OFF
see p. 122
6402 ON-VALUE LOW FLOW CUT
OFF
If you don’t switch off the low flow cut off:
0.0000
see p. 122
6403 OFF-VALUE LOW FLOW CUT
OFF
If you don’t switch off the low flow cut off:
50%
see p. 122
+
+
E
+
E
B
Quick SetupQuick Setup
6400
6402
6403
1004
Esc
E
+
-
XXX.XXX.XX
HOME-POSITION
Assign
Low flow cut off
On-value
Low flow cut off
Off-value
Low flow cut off
QS
Gas measurement