Issue/Rev. 0.2 (12/12) MN0M023 • Page 85
Device Functions Proline Promass 83 7 Block OUTPUTS
Function description
OUTPUTS o PULSE/FREQUENCY OUTPUT (1...2) o CONFIGURATION (PULSE)
ASSIGN PULSE
(4221)
! Note!
This function is not available unless the PULSE setting was selected in the OPERATION
MODE function (4200).
Use this function to assign a measured variable to the pulse output.
Options:
OFF
MASS FLOW
VOLUME FLOW
CORRECTED VOLUME FLOW
Advanced options with optional software package CONCENTRATION:
TARGET MASS
TARGET VOLUME
TARGET CORRECTED VOLUME
CARRIER MASS
CARRIER VOLUME
CARRIER CORRECTED VOLUME
Factory setting:
MASS FLOW
! Note!
If you select OFF, the only function shown in the CONFIGURATION function group is
this function, in other words ASSIGN PULSE (4221).
PULSE VALUE
(4222)
! Note!
This function is not available unless the PULSE setting was selected in the OPERATION
MODE function (4200).
Use this function to define the flow at which a pulse is triggered. These pulses can be
totaled by an external totalizer, and the total flow quantity since measuring started can be
registered in this way.
User input:
5-digit floating-point number [unit]
Factory setting:
depends on nominal diameter and country,
[value] [kg or lb] / impulse;
corresponds to the factory setting for the pulse value (see page 189 ff.).
! Note!
The appropriate unit is taken from the UNIT MASS (0401), UNIT VOLUME (0403) or
UNIT CORRECTED VOLUME (0405) function (see page 17 or page 19).