Device Functions Proline Promass 83 7 Block OUTPUTS
MEASURING MODE
(4246)
! Note!
This function is not available unless STATUS was selected in the OPERATION MODE
function(4200) and the status output was assigned a limit value.
Use this function to define the measuring mode for the status output.
Options:
STANDARD
The status output signal switches at the defined switch points.
SYMMETRY
The status output signal switches at the defined switch points, irrespective of the sign. If
you define a switch point with a positive sign, the status output signal switches as soon as
the value is reached in the negative direction (negative sign), (see illustration).
Factory setting:
STANDARD
Example for the SYMMETRY measuring mode:
Switch-on point Q = 4, Switch-off point Q = 10
m = Status output switched on (conductive)
n = Status output switched off (nonconductive)
A0001247
! Note!
SYMMETRY cannot be selected unless the values in the ON-VALUE (4242) and OFF-
VALUE (4244) functions have the same sign or one of the values is zero.
If the values have different signs, SYMMETRY cannot be selected and an
“ASSIGNMENT NOT POSSIBLE” message is displayed.
TIME CONSTANT
(4247)
! Note!
This function is not available unless the STATUS setting was selected in the OPERATION
MODE function (4200).
Use this function to enter a time constant defining how the measuring signal reacts to
severely fluctuating measured variables, either very quickly (enter a low time constant) or
with damping (enter a high time constant). Damping acts on the measuring signal before
the switch status changes, and consequently before switch-on or switch-off delay is
activated. The purpose of damping, therefore, is to prevent the status output changing
state continuously in response to fluctuations in flow.
User input:
Fixed-point number 0.00 to 100.00 s
Factory setting:
0.00 s
Function description
OUTPUTS o PULSE/FREQUENCY OUTPUT (1...2) o CONFIGURATION (STATUS)
0
-4
-10
4
10
Q
t
➀➁