7 Block OUTPUTS Device Functions Proline Promass 83
7.1 Group CURRENT OUTPUT (1...3)
7.1.1 Function group CONFIGURATION
OUTPUTS E
CURRENT OUTPUT 1 EAA
CONFIGURATION 400
CURRENT OUTPUT 2 EAB
CONFIGURATION 400
CURRENT OUTPUT 3 EAC
CONFIGURATION 400
Function description
OUTPUTS o CURRENT OUTPUT (1...3) o CONFIGURATION
ASSIGN CURRENT
OUTPUT
(4000)
Use this function to assign a measured variable to the current output.
Options:
OFF
MASS FLOW
VOLUME FLOW
CORRECTED VOLUME FLOW
DENSITY
REFERENCE DENSITY
TEMPERATURE
Advanced options with optional software package BATCHING:
BATCH UPWARDS (batching progress upwards)
BATCH DOWNWARDS (batching progress downwards)
! Note!
The current range selected (function CURRENT SPAN (4001)) corresponds to a
batching rate of 0 – 100%, based on the batching quantity.
The batching software automatically sets the values for 0/4 mA and 20 mA (function
VALUE 0_4 mA (4002) and VALUE 20 mA (4003)).
Example with upward batching:
Value 0/4 mA = 0 [unit]; value 20 mA = batching quantity [unit].
Advanced options with optional software package CONCENTRATION:
TARGET MASS FLOW
% TARGET MASS FLOW
TARGET VOLUME FLOW
% TARGET VOLUME FLOW
CORRECTED TARGET VOLUME FLOW
CARRIER MASS FLOW
% CARRIER MASS FLOW
CARRIER VOLUME FLOW
% CARRIER VOLUME FLOW
CORRECTED CARRIER VOLUME FLOW
% BLACK LIQUOR
°BAUME
°API
°PLATO
°BALLING
°BRIX
OTHERS (_ _ _ _ flexible concentration)
(continued on next page)