Issue/Rev. 0.2 (12/12)
Page 164 • MN0M023
10 Block SPECIAL FUNCTION Device Functions Proline Promass 83
10.2.6 Function group INFORMATION
SPECIAL FUNCTION H
BATCHING FUNCTION HCA
CONFIGURATION 720
VALVE PARAMETER 722
SUPERVISION 724
OPERATION 726
INFORMATION 728
Function description
SPECIAL FUNCTION o BATCHING FUNCTION o INFORMATION
INTERNAL SWITCH
POINT
VALVE 1
(7280)
Use this function to display the internal switch point of valve 1 (see function CLOSE
VALVE 1 (7221) on page 153). The value displayed takes the fixed correction quantity
and / or the calculated after run quantity into account.
Display:
max. 7-digit floating-point number [unit]
! Note!
The appropriate unit is taken from the function group SYSTEM UNITS (ACA),
(see page 17).
DRIP QUANTITY
(7281)
Displays the after run calculated (averaged) internally. The value displayed can be
overwritten in this function and the after run can thus be adjusted. The after run quantity
is used to optimize the internal switch point of valve 1.
User input:
0...quantity [unit]
! Note!
The after run, entered in this function, is only used for the first batching process. For the
second and following batching processes, the internally calculated after run will be used
again.
The appropriate unit is taken from the function group SYSTEM UNITS (ACA),
(see page 17).
Factory setting:
0 [unit]
VALVE
1 CLOSING TIME
(7282)
Use this function to display the valve closing time calculated internally.
Display:
max. 7-digit floating-point number [ms]
! Note!
• The valve closing time is the period between the switch point of valve 1 and the first
undershooting of the low flow cut off.
• The data can only be taken as a general trend.