7 Block OUTPUTS Device Functions Proline Promass 83
7.1.2 Function group OPERATION
OUTPUTS E
CURRENT OUTPUT 1 EAA
CONFIGURATION 400
OPERATION 404
CURRENT OUTPUT 2 EAB
CONFIGURATION 400
OPERATION 404
CURRENT OUTPUT 3 EAC
CONFIGURATION 400
OPERATION 404
Function description
OUTPUTS o CURRENT OUTPUT (1...3) o OPERATION
ACTUAL CURRENT
(4040)
Use this function to view the computed actual value of the output current.
Display:
0.00...25.00 mA
SIMULATION CURRENT
(4041)
Use this function to activate simulation of the current output.
Options:
OFF
ON
Factory setting:
OFF
! Note!
The “SIMULATION CURRENT OUTPUT” message indicates that simulation is active.
The measuring device continues to measure while simulation is in progress, i.e. the
current measuring values are output correctly via the other outputs.
" Caution!
The setting is not saved if the power supply fails.
VALUE SIMULATION
CURRENT
(4042)
! Note!
The function is not visible unless the function SIMULATION CURRENT (4041) is active
(= ON).
Use this function to define a freely selectable value (e.g. 12 mA) to be output at the
current output. This value is used to test downstream devices and the measuring device
itself.
User input:
0.00...25.00 mA
Factory setting:
0.00 mA
" Caution!
The setting is not saved if the power supply fails.