Issue/Rev. 0.2 (12/12) MN0M023 • Page 33
Device Functions Proline Promass 83 4 Block QUICK SETUP
• The display returns to the function QUICK SETUP BATCHING/DOSING (1005), if you press
the ESC key combination during parameter interrogation.
• At the start of the Setup, general device parameters are optimally configured for measuring signal
processing and output response.
• Then you can enter the specific batching parameters, starting with the options list “Batching
1...6”. In this way, by running through the Setup menu a number of times, up to six different
batching parameter sets (incl. special naming) can be created and called up as necessary.
• In order to enjoy full functionality, it is advisable to let the display parameters be set
automatically. This means that the lowest display line is configured as the batching menu.
Softkeys are displayed which can be used to start or stop the batching process in the HOME
position. In this way, the measuring device can be fully deployed as a “batch controller”.
"
Caution!
By running the Setup, certain device parameters are optimally set for discontinuous operation.
Should the measuring device be used for continuous flow measurement at a later time, we
recommend you to rerun the “COMMISSIONING” or the “PULSATING FLOW” Setup.
Settings for the Batching Setup menu:
Fct. code Function name Suggested settings Description
Call up through the function matrix:
B QUICK SETUP QUICK SETUP
BATCHING/DOSING
see p. 25
1005 QUICK SETUP BATCHING/DOSING YES see p. 26
Settings (functions with a gray background are set automatically):
6400 ASSIGN LOW FLOW CUT OFF Mass see p. 122
6402 ON-VALUE LOW FLOW CUT OFF Table value see p. 122
6403 OFF-VALUE LOW FLOW CUT OFF 50% see p. 122
6603 FLOW DAMPING 0 seconds see p. 133
6404 PRESSURE SHOCK SUPPRESSION 0 seconds see p. 123
7200 BATCH SELECTOR BATCH #1 see p. 147
7202 BATCH NAME BATCH #1 see p. 147
7201 ASSIGN BATCH VARIABLE Mass see p. 148
7203 BATCH QUANTITY 0 see p. 148
7204 FIX COMPENSATION QUANTITY 0 see p. 149
7205 COMPENSATION MODE OFF see p. 149
7208 BATCH STAGES 1 see p. 152
7209 INPUT FORMAT Value input see p. 152
4700 ASSIGN RELAY BATCHING VALVE 1 see p. 101
4780 TERMINAL NUMBER Output (display only) see p. 107
7220 OPEN VALVE 1 0% or 0 [unit] see p. 153
7240 MAXIMUM BATCHING TIME 0 seconds (Off) see p. 158
7241 MIN. BATCHING QUANTITY 0 seconds see p. 159
7242 MAX. BATCHING QUANTITY 0 seconds see p. 160
2200 ASSIGN (Main line) BATCH NAME see p. 40
2220 ASSIGN (Multiplex main line) Off see p. 42
2400 ASSIGN (Additional line) BATCH DOWNWARDS see p. 44
2420 ASSIGN (Multiplex additional line) Off see p. 47
2600 ASSIGN (Info line) BATCHING KEYS see p. 50
2620 ASSIGN (Multiplex info line) Off see p. 53