Power class Power PSU
4 1600 W AC PSU Platinum
1600 W HVDC PSU 380 V
All different PSUs can be installed, removed or replaced in the same
way.
Assembly rules
Mixed assembly of PSUs from different power classes (e.g. class 1 or class
2) within a system is not supported.
Mixing of Platinum and Titanium PSUs within same class (e.g. class 2)
within a system is not supported.
Mixing of Platinum PSUs within same class and dif
ferent manufacturer (e.g.
class 1) within a system is supported.
Always install a dummy cover into an unused PSU bay to comply with
applicable EMC regulations and satisfy cooling requirements.
For a redundant power supply configuration you need always two PSUs with
the same power class.
Power supply unit (PSU)
RX2530 M6 Upgrade and Maintenance Manual 107