No. Maintenance
Item
Possible Cause Troubleshooting
3 The external
circulation fan
fails to start.
The terminal is
loose.
The power supply
is faulty.
The fan is stuck.
There is no
requirement for
cooling.
1. Check that the power terminal of the fan is
tightened.
2. Check that the voltage of the DC power is
within the operating range.
3. Check that the fan is not stuck by foreign
matters.
4. Check the output status of the fan in the
cabinet.
4 The fan
generates
abnormal noise.
The fan bearing
wears out.
The fan blades
produce friction
sounds.
1. Replace the fan.
2. Check whether the cables hinder fan blade
operation.
5 The compressor
fails to start.
The cable
connection is
loose.
The power is o.
The power supply
is faulty.
The compressor
motor is burned.
There is no
requirement for
cooling.
Shutdown delay
occurs.
The contact of
the compressor
protector is open.
The system high
pressure switch is
turned
o.
1. Secure cable connectors.
2. Check the main power switch.
3. Check that the voltage of the DC power is
within the operating range.
4. Replace the compressor.
5. Check the temperature inside the cabinet.
6. The delay interval for the compressor
startup is 3 minutes.
7. Check whether the contact of the
compressor protector is open.
8. Check whether the external ambient
temperature is too high, whether the air
volume of the external circulation fan is
insucient, and whether the contact of the
high pressure switch is open.
6 The cooling
eect is
unsatisfactory.
The air volume of
the external
circulation fan is
insucient.
Clean the foreign matter on the coil pipe or at
the air intake vent.
iSitePower Integrated Smart Site (ICC1000-A1-E1)
User Manual 4 Maintenance
Issue 04 (2022-10-15) Copyright © Huawei Technologies Co., Ltd. 108