Item Specications
Safety design IEC 60950-1, IEC 62368-1
MTBF 200,000 hours (at 25ºC)
A.3 EMC Specications
Table A-3 EMC specications
Item Specications
Electromagnetic
interference (EMI)
Conducted emission
(CE)
EN 55032
AC port: Class A; DC port: Class A
1
; signal port:
Class A
Radiated emission (RE) EN 55032
Enclosure port: Class A
Harmonic current IEC 61000-3-12
AC power port: The current of each phase is
greater than 16 A.
Voltage uctuation and
icker
AC power port: Pst ≤ 1.0, P1t ≤ 0.65, dc ≤ 3%,
dmax ≤ 4%. The time when the value of d(t)
exceeds 3% is less than or equal to 200 ms.
Electromagnetic
susceptibility (EMS)
Electrostatic discharge
(ESD)
IEC 61000-4-2
Enclosure port: 6 kV (criterion B) contact
discharge; 8 kV (criterion B) air discharge
Electrical fast transient
(EFT)
IEC 61000-4-4
AC power port: 2 kV (criterion B); DC power
port: 2 kV (criterion B); signal port: 1 kV
(criterion B)
Radiated susceptibility
(RS)
IEC 61000-4-3
Enclosure port: The test frequency range is 80–
2700 MHz, 80% AM (1 kHz) modulation is used,
and the test level is 10 V/m.
Conducted susceptibility
(CS)
IEC 61000-4-6
Power port: 10 V
Signal port: 3 V
iSitePower Integrated Smart Site (ICC1000-A1-E1)
User Manual A Technical Specications
Issue 04 (2022-10-15) Copyright © Huawei Technologies Co., Ltd. 161