Table 2-1 Key functions
No. Item Description
1 Mains
management
Wide operating voltage range
Supports 85–300 V mains input.
Mains protection
Supports mains overvoltage protection. The
overvoltage protection threshold is 300 V.
Supports mains undervoltage protection. The
undervoltage protection threshold is 84 V.
Mains alarm management
Reports alarms for mains overvoltage,
undervoltage, and mains absence.
2 Solar power
management
Wide operating voltage range
Works properly at 24–140 V.
High-precision tracking
The tracking precision of the MPPT function
reaches up to 99.8%.
High
eciency
MTTP's eciency reaches up to 98%.
3 Multi-energy
collaboration
management
Solar-mains collaboration
Based on the status of the solar energy and
mains supply, the solar energy is preferentially
used to ensure that the system works in the
most economical way.
4 M48500N1 output
management
12 V DC
Provides 12 V DC output and supports remote
reset.
24 V DC
Provides 24 V DC output and supports remote
reset.
24V AC
Provides 24 V AC output and supports remote
reset.
5 Signal port
management
One alarm output port
One dry contact input port
6 Local wired
maintenance
Supports local wired maintenance.
7 Battery state of
health (SOH)
management
Supports battery state of charge (SOC) and SOH
management.
iSitePower Integrated Smart Site (ICC1000-A1-E1)