(7) SPD (8) DG 1 input circuit breakers (9) Mains/DG 2 input circuit
breakers
Functions
The ATS is an automatic switch system integrating control and power distribution.
It supports and detects the three-phase inputs from two power sources (DG 1 and
mains or DG 1 and DG 2) and switches between the two power inputs. The power
source can switch to DG 1 by turning the bypass switch. The following table
describes the ATS functions.
Table 3-51 ATS function description
Function Description
Rated input
power
200 V–240 V/346 V–415 V; three-phase; 50 Hz/60 Hz; max.
63 A
Rated output
power
200 V–240 V/346 V–415 V; three-phase; 50 Hz/60 Hz; max.
63 A
AC power
distribution
Provides one route of three-phase AC power distribution for
downstream loads, one 10 A AC output, and one reserved
maintenance socket output.
Power source
switching
Provides a bypass switch that allows the power source to
switch to DG 1.
Monitoring Monitors the voltage, current, frequency, and power factor
of three-phase outputs.
Protection Protects against mains overvoltage, mains undervoltage,
DG overvoltage, and DG undervoltage.
Alarming Generates alarms for mains open phase and DG open
phase.
AC surge
protection
Nominal discharge current In: 20 kA (8/20 µs); maximum
discharge current Imax: 40 kA (8/20 µs)
Port surge
protection
Alarm port: 5 kA, 8/20 µs; in-cabinet CAN port: 250 A, 8/20
µs
Technical Specications
Table 3-52 ATS technical specications
Item
Specications
Dimensions (H x W x D) 175 mm x 482.6 mm x 310 mm (including mounting
ears)
Weight 20 kg
iSitePower Integrated Smart Site (ICC1000-A1-E1)
User Manual 3 Components