WindO/I-NV4 User’s Manual 10-119
6 Message Switching Display
10
Data Displays
6.3 Properties of Message Switching Display Dialog Box
This section describes items and buttons on the properties dialog box.
●
General Tab
■ Part Name
Enter a name for the part. The maximum number is 20 characters.
■ Switching Method
Selects the method for switching message to display from the following. Messages are registered in Settings on the
Message tab.
Bit Number: Switches the message to display according to the status of bits in a device address.
Example: When Bit Number is selected and the bits of trigger device address D0 are allocated to the
following messages.
Switches the message to display according to the status of the bits.
bit15 bit0
bit3
Trigger device address D0
Msg0
Drying
Heating
Cooling
Msg1
Msg2
Message
0001
Message to display
0010 0100
1000
Display Msg0
Action
Display Msg1 Display Msg2
1110
Display Msg1
No message
Msg0 Msg1 Msg2 Msg1
Bit state of
Trigger Device Address D0
Drying Heating Cooling Heating
If all bits in the device address are 0 or if a
bit with no associated message becomes 1,
display nothing.
If multiple bits are 1, display the
message for the lowest order bit.