WindO/I-NV4 User’s Manual 12-59
7 Timer
12
Commands
7.1 How the Timer is Used
Starts a countdown when the trigger condition is satisfied, and writes 1 to an internal device (HMI Timer Relay LTC)
once the set time has elapsed.
7Timer
HG3G
HG2G-5FHG5G-V HG4G-V HG3G-V HG2G-V HG2G-5T
HG4G HG1G HG1P
MICRO/I
LTD0
0
1
LTC0:
0
LTC0:
1
1999
1998 999 1
0
LTD0
Start countdown Set me
has elapsed
Condition
Satisfied
Satisfied
Satisfied
Start
countdown
0 0 1 0
Writes 1
to LTC0
Writes the
preset value
to LTD0 and 0
to LTC0
State of condition
Action
HMI Timer Relay
LTC0 value
HMI Timer Current Value
LTD0 value
1999
1999
1998 999 1
1999
0
Condition Condition Condition Condition
Not satisfiedNot satisfiedNot satisfied SatisfiedSatisfiedSatisfied SatisfiedSatisfiedSatisfied
Not satisfiedNot satisfiedNot satisfied
• The HMI Timer Relay LTC is an internal device (bit device) that changes to 1 once the time set for the
timer has elapsed.
• The HMI Timer Current Value LTD is an internal device (word device) that stores current values for the
timer.
• Once switched to the screen that the timer has been placed in, the following values will be given
regardless of the whether the trigger condition is satisfied or not satisfied.
-HMI Timer Relay LTC: 0
- HMI Timer Current Value LTD: Preset Value

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IDEC MICRO/I HG1P-ST32 Series and is the answer not in the manual?

IDEC MICRO/I HG1P-ST32 Series Specifications

General IconGeneral
BrandIDEC
ModelMICRO/I HG1P-ST32 Series
CategoryControl Panel
LanguageEnglish

Related product manuals