WindO/I-NV4 User’s Manual 10-191
10 Calendar
10
Data Displays
■ ON Time
Configures the time to write 1 to the Report Device Address according to the type of data.
■ OFF Time
Select this check box to configure the time to write 0 to the Report Device Address.
The time is configured according to the type of data.
■ Report Device Address
Specifies the bit device to write the value to at ON Time and OFF Time.
Click to display the Tag Editor. For the device address configuration procedure, refer to Chapter 2 “5.1 Device
Address Settings” on page 2-68.
• After 1 is written to the Report Device Address with ON Time, that value is retained.
• After a screen configured with the Calendar is displayed, if the time is in between ON Time and OFF
Time, 1 is written to the Report Device Address.
Value of device address retained after ON Time elapses
1
0
09:00
09:30 10:00 10:30 11:00
Report Device Address
M0 value
Time
ON Time
Turn on MICRO/I power
Open screen
1
0
09:00
09:30 10:00 10:30 11:00
Report Device Address
M0 value
Time
ON Time
Writes 1 to notify that ON Time has already elapsed
OFF Time
• The value of Report Device Address is retained even when the current time exceeds OFF Time.
• After a screen configured with the Calendar is displayed, if the time exceeds OFF Time, 0 is written to
the Report Device Address.
Value of device address retained after OFF Time elapses
1
0
10:00
10:30 11:00 11:30 12:00
Report Device Address
M0 value
Time
OFF Time
Turn on MICRO/I power
Open screen
Report Device Address
M0 value
1
0
Time
10:00 10:30 11:00 11:30 12:00
OFF Time
Writes 0 to notify that OFF Time has already elapsed
ON Time