3 Alarm Log Settings Dialog Box
13-30 WindO/I-NV4 User’s Manual
While the beep is sounding, System Area 1 (address number+1, bit 6) is 1.
While the screen is flashing, System Area 1 (address number+1, bit 2) is 1.
To stop the sound of the buzzer and the screen flashing when an alarm has occurred, use the following
methods.
- Press the key button Stop the Sound of the Buzzer and Screen flashing
- When a condition selected with the Stop the Sound of the Buzzer and Screen flashing check
boxes is satisfied
- To stop the sound of the buzzer, set System Area 1 (address number+1, bit 6) to 0
- To stop the screen flashing, set System Area 1 (address number+1, bit 1 to 4) to 0
However, when System Area 1 (address number+1, bit 6) is 1 for a reason other than the occurrence of
an alarm, the sound of the buzzer does not stop until 0 is written. When System Area 1 (address
number+1, bit 1 to 4) are 1, the alarm is triggered, however, the screen flashing doesn't stop until 0 is
written into it.
If you stop the screen flashing, the backlight turns off when System Area 1 (address number+1, bit 0),
and the backlight turns on when it is 1.