EasyManua.ls Logo

Inovance MD800 Series - Preparations Before Installation; 2.1 Installation Procedure

Inovance MD800 Series
565 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
List of Power Supply Unit Parameters
Para.
No.
Address
Name
Value Range
Default
Unit
Change
Page
F5-01 62721
DO1/RO1 function
0: No function
1: Ready to run
2: Fault
3: Warning
4: Circuit breaker action
5: Bus undervoltage
6: Bus overvoltage
7: Bus voltage normal
8: Three-phase input
abnormal
9: Three-phase input normal
10: Output upon IGBT
overtemperature
11: Output upon IGBT
overtemperature pre-
warning
12: Communication control
0 -
At stop
F5-01
on
page 48
F5-02 62722
DO2/RO2 hardware source
Same as F5-00 0 -
At stop
F5-02
on
page 49
F5-03 62723
DO2/RO2 function selection
Same as F5-01 0 -
At stop
F5-03
on
page 49
F5-04 62724
DO3/RO3 hardware source
Same as F5-00 0 -
At stop
F5-04
on
page 49
F5-05 62725
DO3/RO3 function
Same as F5-01 0 -
At stop
F5-05
on
page 49
F5-06 62726
DO4/RO4 hardware source
Same as F5-00 0 -
At stop
F5-06
on
page 50
F5-07 62727
DO4/RO4 function
Same as F5-01 0 -
At stop
F5-07
on
page 50
F5-08 62728
DO5/RO5 hardware source
Same as F5-00 0 -
At stop
F5-08
on
page 50
F5-09 62729
DO5/RO5 function
Same as F5-01 0 -
At stop
F5-09
on
page 50
F5-10 62730
DO1/RO1 active delay
0.00s to 600.00s 0.00 s At once
F5-10
on
page 50
F5-11 62731
DO2/RO2 active delay
0.00s to 600.00s 0.00 s At once
F5-11
on
page 51
F5-12 62732
DO3/RO3 active delay
0.00s to 600.00s 0.00 s At once
F5-12
on
page 51
F5-13 62733
DO4/RO4 active delay
0.00s to 600.00s 0.00 s At once
F5-13
on
page 51
F5-14 62734
DO5/RO5 active delay
0.00s to 600.00s 0.00 s At once
F5-14
on
page 51
-12-

Table of Contents