Parameter Group
-220-
Default:
10.00
Change:
At once
Value Range:
0.00% to 100.00%
Description
This parameter defines the auxiliary frequency reference coefficient when the frequency
superposition mode is Main x Auxiliary. The value 100.00% corresponds to the target auxiliary
frequency reference.
F0-29
G/P model
Address:
61469
Min.:
1
Unit:
-
Max.: 2 Data type: UInt16
Default:
1
Change:
At stop
Value Range:
1 to 2
Description
1: G type (constant-torque load)
The G type models typically carry constant-torque loads with large overload capacity. The overload
capacity is 150% in general. Such loads include conveyor belts and cranes, for example.
2: P type (fan and pump)
2.2 F1: Motor 1 Parameters
F1-00
Motor type selection
Address:
61696
Min.:
0
Unit:
-
Max.: 2 Data type: UInt16
Default:
0
Change:
At stop
Value Range:
0: Common asynchronous motor
1: Variable frequency asynchronous motor
2: Synchronous motor
Description
A variable frequency motor can adjust its frequency and speed according to the load. Where the
voltage is low, it can reduce the frequency and start reliably. Where the load is light, it can reduce the
frequency, speed, and current to save electric energy.
A common asynchronous motor is suitable for applications with normal voltage but often full load. It
is designed based on constant frequency and constant voltage. Therefore, it may not meet all the
frequency and speed control requirements.
F1-01
Rated motor power
Address:
61697
Min.:
0.1
Unit:
kW
Max.: 1000.0 Data type: UInt16
Default:
Model dependent Change:
At stop
Value Range:
0.1 kW to 1000.0 kW