Parameter Group
-85-
Description
This parameter defines the parameters to be backed up.
FP-07
Local parameter backup operation
Address:
7943
Min.:
11
Unit:
-
Max.: 28 Data type: UInt16
Default:
0
Change:
At once
Value Range:
Ones: Drive unit axis number
1 to 8
Tens: Backup operation
1: Read
2: Write
Description
This parameter defines the axis to be backed up and the backup type.
1.8 A0: Internal Communication Parameters
A0-00
I/O extension card communication cycle
Address:
40960
Min.:
0
Unit:
-
Max.: 100 Data type: UInt16
Default:
0
Change:
At once
Value Range:
0 to 100
Description
This parameter defines the communication cycle of the I/O extension card.
A0-01
Alarm threshold of consecutive drive unit frame loss
Address:
40961
Min.:
0
Unit:
-
Max.: 1000 Data type: UInt16
Default:
10
Change:
At once
Value Range:
0 to 1000
Description
This parameter defines the allowed maximum number of I/O communication data frames lost by the
drive unit.
When the consecutive frame loss count of the drive unit exceeds the value of A0-01, the system
reports A98.01.
When the consecutive frame loss count of the I/O extension card exceeds the value of A0-02 and the
consecutive frame loss count of the drive unit exceeds the value of A0-01, the system reports A98.03.
A0-02
Alarm threshold of consecutive I/O extension card frame loss
Address:
40962
Min.:
0
Unit:
-
Max.: 1000 Data type: UInt16
Default:
10
Change:
At once
Value Range: